products

Standard 3P Manual Output Breaker AC Perkins 50Hz Diesel Generating Sets

Basic Information
Place of Origin: Dongguan China
Brand Name: LionRock
Model Number: LRP400
Minimum Order Quantity: negotiate
Price: negotiate
Packaging Details: export packing
Delivery Time: negotiate
Payment Terms: TT
Detail Information
Frequency: 50Hz Length: 3500
Width: 1150 Height: 2158
Weight: 3150 Fuel Tank: 880

Product Description

LionRock Generator sets are suitable for commercial, industrial, telecom, Data Centre and infrastructure application.

 

Standard features

- Set mount radiator with engine driven fan
- Cooling system standard for 40°C ambient
- Anti-vibration mounts between engine / alternator and baseframe
- Baseframe fuel tank
- Protective grille for fan and rotating parts
- Exhaust bellow and industrial silencer
- 24VDC starter motor and battery
- Generator sets are CE Certified
- Standard 3P manual output breaker
- Coolant and oil drains with valve
-
Each LionRock® generating set will go through factory test at 0%, 25%, 50%, 75%, 100% and 110% of rated capacity

 

Standard and Quality

- All generator sets comply with international standards including ISO8528, ISO3046, IEC60034, BS5000
- Manufacturing standard certified to ISO9001, ISO14001, ISO18001

- CE certificate for generator set

 

Rating definition as per ISO8528

- Prime - Output available with varying load for an unlimited time. Average power output is 70% of the prime power rating. Typical peak demand    is 100% of prime rated kWe with 10% overload capability for emergency use for a maximum of 1 hour in 12.
- Standby - Output available with varying load during a normal power supply failure. Average power output is 80% of the standby power rating.    Typical annual operating time less than 500hours. No overload is available.

 

Power                                                                                  Ratings at 0.8 power factor
Voltage(V)
Standby

 

Prime

 

Maximum current(Amp)
kVA
kW
kVA
kW
380/220
400
320
355 284 608
400/230
400
320
355 284 577
415/240
400
320
355 284 556

 

Fuel Consumption
Load (%)
Standby
100 75 50
(L/h)
86 78 60 43

 

Standard 3P Manual Output Breaker AC Perkins 50Hz Diesel Generating Sets 0

Dimensions
Weight
Fuel Tank
Length (L)
Width (W)
Height (H)
Dry
Baseframe
mm
mm 
mm
kg
litres
3500 1150 2158 3150 880

 

Control System
 
Technical data
 
Electrical measurement
- Voltage (P-P, P-N)
- Current
- Frequency
- Power factor
 
Energy Meter
- kW
- kWh
- kVA
 
Mechanical measurement
- Water temperature
- Oil Pressure
- Engine speed
- Running hours
- Number of start
- Battery voltage
 
Protection
Mechanical
- Overspeed
- High coolant temperature
- Low oil pressure
- Start up failure lock out
- Emergency Stop
Electrical
- Over and under frequency
- Over and under voltage
- Overload
- Overcurrent
- Power factor
- Current unbalance
 
Communication
- USB (Programming)
 
Control
- Auto/Manual
- Start/stop button
- Alarm/fault acknowledge
- Menu button
- Display navigation buttons
 
Features
- Automatic mains failure
- Fuel tank content in %
- Oil temperature gauge
- Modbus SNMP
- Modbus TCP/IP Ethernet
- Extended input/output modules
- RS485 Modbus
 
Alternative control modules
- Wide range of control module options including:
ComAp
Deepsea
Woodward
Smartgen etc.
- Multiple generators parallel as well as parallel with mains power
 
Soundproof Canopy
 
Standard 3P Manual Output Breaker AC Perkins 50Hz Diesel Generating Sets 1
Dimensions and Weights
Length (L): mm
4760
Width (W): mm
1620
Height (H): mm
2230
Weight: kg
4435
Fuel Tank Capacity: litres
880

 

Sound Pressure Levels
75% Load
50Hz
Prime: dBA@1m
87
           dBA@7m
77
           dBA@15m
71

 

Stainless steel locks and handles on doors
- Black zinc die cast hinges on doors proven to withstand extreme weather conditions
- Zinc plated standard fastener with stainless steel option
- Enclosure made of sheet steel pre-treated with zinc phosphate prior to polyester powder coating
 
Secure, lockable doors prevent unauthorized access to control panel, fuel fill and battery
- Emergency stop buttons mounted on enclosure exterior surface
- All moving parts including Cooling fan, charging alternator, belt are fully guarded
 
Hinged doors of 180 deg swing on both sides of the enclosure for easy access and maintenance
- Lube oil and water drains hosed to baseframe side to exterior
- Removable end panels allow access to radiator, exhaust silencer and alternator rear
- Exhaust silencer inside enclosure
 
Easy Transportable
- Lifting points on both side of baseframe
- Anchor and drag points at baseframe ends

Contact Details
dgmarketing

Phone Number : +8613160961036