Nominal Voltage: | 12 V | Capacity: | 170 Ah @ 10hr To 1.80 V Per Cell @ 25˚C (77˚F) |
---|---|---|---|
Weight: | 54 Kg (119.05 Ibs) | Length: | 559 Mm (22.01 In) |
Width: | 125 Mm (4.92 In) | Height: | 315 Mm (12.40 In) |
High Light: | 170 Ah VRLA 12v Battery,ABS VRLA 12v Battery |
Save Floor Space 6-FMX Series VRLA Battery
Benefits
- Front terminal design, easy access for faster installation and maintenance
- Optimal energy density, save floor space
- No leakage and no acid smog spray during the operation
Main Applications
- Telecom site
- Outdoor base station
- Floating operation site
- UPS
Technical Features
- Excellent capacity retention rate
- Long life float service design
- Excellent over discharge recovery capability
Certification
- ISO 9001:2008
- ISO 14001:2004
- GB/T 28001-2011
- UL
- CE
Technical Parameters
Nominal Voltage | 12 V |
Capacity | 170 Ah @ 10hr to 1.80 V per cell @ 25˚C (77˚F) |
Weight | 54 kg (119.05 Ibs) |
Dimensions | Length: 559 mm (22.01 in) Width: 125 mm (4.92 in) Height: 315 mm (12.40 in) |
Internal Resistance (full charged) | 3.7mΩ |
Short - circuit Current | 2607 A |
Self Discharge @25˚C (77˚F) | Less than 4% after 30 days storage |
Operating Temperature Range | Discharge: -40˚C~50˚C (-40˚F~122˚F) Charge: -20˚C~45˚C (-4˚F~113˚F) Storage: -20˚C~40˚C (-4˚F~104˚F) |
Recommended Operating Temperature | 15˚C~25˚C (59˚F~77˚F) |
Recommended Charging Current | 34 A |
Charging Voltage @25˚C (77˚F) | Float: 2.23 V/cell Equalize: 2.35 V/cell |
Terminal | M6 |
Container Materials | ABS/ABS V0 (Optional) |
Capacity Affected by Temperature (C10) | 103% @ 40˚C (104˚F) 85% @ 0˚C (32˚F) 60% @ -20˚C (-4˚F) |
Design Life @25°C (77˚F) | 12 years |