Nominal Voltage: | 12 V | Capacity: | 200 Ah @ 10hr To 1.80 V Per Cell @ 25˚C (77˚F) |
---|---|---|---|
Weight: | 56.5 Kg (124.56Ibs) | Length: | 559mm (22.01 In) |
Width: | 125mm (4.92 In) | Height: | 315mm (12.40 In) |
High Light: | 559mm VRLA 12V Battery,VRLA 12V Battery 200Ah,LionRock VRLA Battery 200Ah |
Front Terminal Design 6-FMX Series VRLA Battery
Benefits
- Front terminal design, easy access for faster installation and maintainence
- Optimal energy density, save floor space
- No leakage and no acid smog spray during the operation
Main Applications
- Telecom site
- Outdoor base station
- Floating operation site
- UPS
Technical Features
- Excellent capacity retention rate
- Long life float service design
- Excellent over discharge recovery
- Capability
Certification
- ISO 9001
- ISO 14001
- GB/T 28001
- UL
- CE
Technical Parameters
Nominal Voltage | 12 V |
Capacity | 200 Ah @ 10hr to 1.80 V per cell @ 25˚C (77˚F) |
Weight | 56.5 kg (124.56Ibs) |
Dimensions | Length: 559mm (22.01 in) Width: 125mm (4.92 in) Height: 315mm (12.40 in) |
Internal Resistance (full charged) | 3.6mΩ |
Short - circuit Current | 2852 A |
Self Discharge @25˚C (77˚F) | Less than 4% after 30 days storage |
Operating Temperature Range | Discharge: -40˚C~50˚C (-40˚F~122˚F) Charge: -20˚C~45˚C (-4˚F~113˚F) Storage: -20˚C~40˚C (-4˚F~104˚F) |
Recommended Operating Temperature | 15˚C~25˚C (59˚F~77˚F) |
Recommended Charging Current | 40 A |
Charging Voltage @25˚C (77˚F) | Float: 2.23 V/cell Equalize: 2.35 V/cell |
Terminal | M6 |
Container Materials | ABS/ABS V0 (Optional) |
Capacity Affected by Temperature (C10) | 103% @ 40˚C (104˚F) 85% @ 0˚C (32˚F) 60% @ -20˚C (-4˚F) |
Design Life @25°C (77˚F) | 12 years |